Health & Environmental Research Online (HERO)


Print Feedback Export to File
5070968 
Book/Book Chapter 
Removal of iron and manganese from groundwater: a study of using potassium permanganate and sedimentation 
Elsheikh, M; Guirguis, H; Fathy, A 
2018 
MATEC Web of Conferences 
162 
Experiments are done for different combinations of Fe+2 and Mn+2 concentrations. The obtained results show that Potassium Permanganate (PP) gives good results in iron and manganese removal. By using PP dose near to half of the theoretically required one, it can remove up to 100 % and 90 % of iron and manganese, respectively over different tested concentrations at pH=7.0. Increasing rate of filtration influences the Mn+2 removal process obviously. Sedimentation is required when combined concentrations of iron and manganese are greater than 5.0 ppm to reduce filter rapid clogging. Using conventional treatment with adding alum, flocculation, sedimentation and filtration can remove up to 97% and 18% of iron and manganese, respectively. Using PP in addition to alum enhances manganese removal but decreases iron removal. However, using alum with increasing pH to 10 leads to 100 % and 95 % of Fe+2 and Mn+2 removal and increases filter working period.