Experimental study on an adsorption chiller employing lithium chloride in silica gel and methanol 
Gong, LX; Wang, RZ; Xia, ZZ; Lu, ZS 
2012 
Yes 
International Journal of Refrigeration
ISSN: 0140-7007 
35 
1950-1957 
A novel composite adsorbent methanol adsorption chiller was proposed and manufactured. It was filled by the adsorbent composed by Lithium Chloride and silica gel. Methanol was used as adsorbate and refrigerant. Experiment results showed that compared with silica gel-water chiller, SCP (specific cooling power) and COP (coefficient of performance) of this novel chiller were improved by 16.3% and 24.2% separately when the temperatures of hot water inlet, cooling water inlet and chilled water outlet were 85 degrees C, 30 degrees C and 15 degrees C. (C) 2012 Elsevier Ltd and IIR. All rights reserved. 
Adsorption system; Performance; Lithium chloride; Silica gel; Methanol 
IRIS
• Methanol (Non-Cancer)
     Search Jan 30 2013
          WOS